WebAug 13, 2024 · As for the frequency the motor will run at a different speed 50 / 60hz. RPM is based on the number of poles and the frequency. You CAN run a motor on a foreign voltage and frequency. Just be mindful that the amps and RPM will NOT be the same as the nameplate. No VFD is needed unless your application is speed sensitive. WebJun 17, 2012 · Example: A 60Hz 240Vac motor is going into 50Hz service. V/f = Y Hence: 240/60 = 4.0. So if Y x f = V then by plugging in the new frequency of 50 we see: 4.0 x 50 = V. V = 200. Running the motor at 200V at 50Hz will remove the V/f problem. Another way to think of this is: New voltage = Old voltage x 50/60.
Can I Use 60 Hz Motor On 50Hz Supply? - YouTube
http://www.50hz60hz.com/ WebDec 12, 2024 · The ratio of Voltage and Frequency is exactly the same (400/50 = 8.0, 480/60 = 8.0), so the motor will work at 480V 60Hz and provide it's full rated torque at nameplate FLA without issue. But the problem is with the load. Most likely your dust collection blower is a centrifugal type. lvt intratech. jsc
Running 60 Hz motors on 50 Hz - Bright Hub Engineering
http://www.50hz60hz.com/460v-60hz-motor-on-400v-50hz-power-supply.html WebOct 27, 2024 · If saturation is more than 20% away at 60Hz, then you'll get away with it at 50Hz. If closer, then the core could saturate, drawing many times more current. You can avoid this by transforming the voltage … WebJul 26, 2024 · Can I use 60 Hz motor on 50Hz supply? For a generic answer: yes you can, IF: you reduce the voltage by 50/60, the equipment doesn’t care, you don’t care about … lvt importers in north america